Boiler room with two heat exchangers

Boiler room with two heat exchanger

The boiler , with two exchangers, is intended for installations where there is a second, auxiliary energy source, such as oil, gas, solid fuel boilers, etc. When there is no sun even then there is hot water. All boilers , are vertical with a leatherette casing , or even with a steel casing , in case of installation outdoors. Sigma Energy, has the know-how for studies of central systems for both domestic, commercial and industrial use.

Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 3 m2
Exchanger surface S1 0,6 m2
Exchanger  surface S2 0,75 m2
Exchanger power S1
solar = 80°
ΔT water use: 15° / 60° C)
13,1 kw
900 l/h
Exchanger power S2
solar = 80°
ΔT water use: 15° / 60° C)
10,4 kw
900 l/h
Electrical resistance power 4 kw
Cold water inlet 1″
Cold water oulet 1″
Recirculation 1″
Weight 70 kg
Height 1280 mm
Diameter 530 mm
Insulation thickness 55 mm
Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 4 m2
Exchanger surface S1 0,75 m2
Exchanger surface S2 0,90 m2
Exchanger power S1
solar = 80°
ΔT water use: 15° / 60° C)
14,4 kw
900 l/h
Exchanger power S2
solar = 80°
ΔT water use: 15° / 60° C)
13,6 kw
900 l/h
Electrical resistance power 4 kw
Cold water inlet 1″
Cold water outlet 1″
Recirculation 1″
Weight 100 kg
Height 1260 mm
Diameter 580 mm
Insulation thickness 55 mm
Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 6 m2
Exchanger surface S1 1 m2
Exchanger surface S2 1,6 m2
Exchanger power S1
solar = 80°
ΔT water use: 15° / 60° C)
23 kw
900 l/h
Exchanger power S2
solar = 80°
ΔT water use: 15° / 60° C)
16,4 kw
900 l/h
Electrical resistance power 4 kw
Cold water inlet 1″
Cold water outlet 1″
Recirculation 1″
Weight 130 kg
Height 1770 mm
Diameter 580 mm
Insulation thickness 55 mm
Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 10 m2
Exchanger surface S1 1,20 m2
Exchanger surface S2 2 m2
Exchanger power S1
solar = 80°
ΔT water use: 15° / 60° C)
25,8 kw
900 l/h
Exchanger power S2
solar = 80°
ΔT water use: 15° / 60° C)
19,2kw
900 l/h
Electrical resistance power 6 kw
Cold water inlet 1“
Cold water outlet 1“
Recirculation 1″
Weight 170 kg
Height 1770 mm
Diameter 700 mm
Insulation Thickness 55 mm
Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 16 m2
Exchanger surface S1 1,4 m2
Exchanger surface S2 2,4 m2
Exchanger power S1
ηλιακών = 80°
ΔT water use: 15° / 60° C)
30 kw
900 l/h
Exchanger power S2
solar = 80°
ΔT water use: 15° / 60° C)
20,5 kw
900 l/h
Electrical resistance power 6 kw
Cold water inlet 1½“
Cold water outlet 1½“
Recirculation 1″
Weight 250 kg
Height 1800 mm
Diameter 1000 mm
Insulation thickness 100 mm
Exchanger S1 input/output 1″
Maximum proposed collector surface of solar panels 20 m2
Exchanger surface S1 1,97 m2
Exchanger surface S2 3 m2
Exchanger power S1
solar = 80°
ΔT water use: 15° / 60° C)
38,5 kw
900 l/h
Exchanger power S2
ηλιακών = 80°
ΔT water use: 15° / 60° C)
25,5 kw
900 l/h
Electrical resistance power 2×6 kw
Cold water inlet 1½“G
Cold water outler 1½“ G
Recirculation 1″
Weight 276 kg
Height 2000 mm
Diameter 1000 mm
Insulation thickness 100 mm